Navya Sharma // personal site
← projects

Hardware · 2026

Lam Research Challenge 3.0 — an automated dosing plant, built three times

A national engineering contest about dosing exact volumes, in order, without overshooting. A worked written round, then a rig built from a posted kit, then a two-day Grand Finale in Bengaluru, where our final run went through without a fault.

ESP32Arduino C++PythonpyserialP&ID (ISA-5.1)

Lam Research Challenge 3.0 is a national engineering contest run in three rounds, and the problem in all three is the same one a real process plant has: put exact volumes of liquid into a vessel, in a fixed order, automatically, and stop before you overshoot — because what has gone in cannot be taken out. I entered with a team of four as Team Hyryders.

Stage 1: on paper

A written technical assessment. We answered it as a worked set of solutions.

Stage 2: a rig at home

The organisers posted each team a kit: three pumps, three tanks, a solenoid valve, a YF-S401 flow transmitter, a float switch and an ESP32 control board. The solenoid driver arrived broken and its lead was missing. From that kit we had to build, commission, calibrate and demonstrate a small automated dosing rig, and submit a P&ID, the code, written answers and two videos.

I drew the P&ID to ISA-5.1 using only the parts in the kit, then a wiring diagram for the board, the drivers and the sensors. Drawing the wiring caught a fault before anything was built: the flow transmitter's 5 V pulse ran straight into a 3.3 V pin with no divider. The rig was built, debugged and calibrated over four days. Every interlock was left on in the firmware, and the entry went in on 18 October 2026 as a 45-page document: first what the paper asked for, then the extras, including a component-level circuit and a proposed controller board.

The Grand Finale: two days in Bengaluru

Twenty-five teams, the same kit each, and a target colour each. Ours was Crimson: about 3,000 mL mixed from red, blue and yellow at 80/10/10, with each line held to ±2 % of its own dose and all of it started from a single switch. Day 2 raised the bar. One press of START had to flush a line with exactly 2 L of water, make a 10 °C difference between two tanks, and then dose all three colours in one closed-loop run, with no hands between steps and a trip on an empty tank, no flow or a full mixing tank.

I rewrote the plant program the night before Day 2: a program on the laptop that drives the two ESP32s and keeps a record of every run, so the logged data the judges asked for came straight from it. The final run went through without a fault: 2 L flushed, ΔT reached, all three colours dosed, every step ending on its own.

We finished outside the top three. Looking back, the Day 1 run that failed perhaps cost us the place.

What it taught

  • Trust time over pulses on cheap flow sensors. Red's real volume followed how long the pump ran, while its pulse count read high. Blue's pulse rate rose by about a quarter once the liquid was cooled. In the last run, two of the three lines were dosed by time for this reason.
  • The measuring jar was the limit, not the code. It reads to about 20 mL, so at 300 mL the true error can be several percent, against a ±2 % target. Measuring the measurement comes before tuning anything.
  • A rewrite the night before can work, but it leaves no slack. The new code met real hardware for the first time on the judged day, and calibration ran until 14:46 against a 15:30 close.